1、风机允许全(quan)压(ya)(ya)起(qi)动(dong)或降压(ya)(ya)电(dian)(dian)动(dong),但应(ying)注(zhu)意,全(quan)压(ya)(ya)起(qi)动(dong)时的电(dian)(dian)流约(yue)为5-7倍的额定电(dian)(dian)流,降压(ya)(ya)起(qi)动(dong)转矩(ju)与电(dian)(dian)压(ya)(ya)平(ping)方(fang)成正比,当电(dian)(dian)网容(rong)量不足时,应(ying)采用(yong)降压(ya)(ya)起(qi)动(dong)。
2、在试(shi)车时(shi),应认(ren)(ren)真(zhen)阅读产品说(shuo)明书(shu),检查(cha)接(jie)(jie)线方(fang)法是(shi)否(fou)同(tong)接(jie)(jie)线图相(xiang)符;应认(ren)(ren)真(zhen)检查(cha)供给(ji)风(feng)机(ji)(ji)(ji)电源的工作电压(ya)是(shi)不(bu)(bu)(bu)是(shi)符合要求(qiu),电源是(shi)否(fou)缺相(xiang)或同(tong)相(xiang)位,所配电器元件的容(rong)量是(shi)否(fou)符合要求(qiu)。 3、试(shi)车时(shi)人数不(bu)(bu)(bu)少于两(liang)人,一人控制电源,一人观察风(feng)机(ji)(ji)(ji)运(yun)转情(qing)况,发现(xian)(xian)异常现(xian)(xian)象及时(shi)停机(ji)(ji)(ji)检查(cha);先检查(cha)旋转方(fang)向是(shi)否(fou)正确(que)(que);离心风(feng)机(ji)(ji)(ji)开始(shi)运(yun)转后(hou),应检查(cha)各相(xiang)运(yun)转电流是(shi)否(fou)平衡、电流是(shi)否(fou)大于额定电流;若有不(bu)(bu)(bu)正常现(xian)(xian)象,应停机(ji)(ji)(ji)检查(cha)。运(yun)转五分(fen)钟后(hou),停机(ji)(ji)(ji)检查(cha)风(feng)机(ji)(ji)(ji)是(shi)否(fou)有异常现(xian)(xian)象,确(que)(que)认(ren)(ren)无异常现(xian)(xian)象再开机(ji)(ji)(ji)运(yun)转。
4、试车时,应先起动低速,检查旋转方向是否正确;起动高速时要待风机静止后再启动,以免高速反向旋转,引起开关跳闸及电机受损。
5、离心风机达到正常转速时,应测量风机输入电流是否正常,离心风机的运行电流不能大于其(qi)额定电流。若运行电流大于其(qi)额定电流,应检查供给的电压是否(fou)正常。
6、对离心风(feng)机(ji)和风(feng)机(ji)箱(xiang),进风(feng)口全(quan)开时(shi)所(suo)需(xu)功率(lv)较(jiao)大。若进风(feng)口全(quan)开进行运(yun)转,则电机(ji)有损坏的危险。
风机试车时尽量(liang)将(jiang)风机入口或(huo)出口管道上(shang)的(de)阀门(men)(men)关(guan)闭,运(yun)(yun)转后将(jiang)阀门(men)(men)渐(jian)渐(jian)开启,达到所需工况(kuang)为止(zhi),并注意(yi)风机的(de)运(yun)(yun)转电流(liu)是否大于额定电流(liu)。