一、风(feng)机盘管系统的(de)监控功能要点
1、室内温度测量;
2、冷、热(re)水阀开关控(kong)制(zhi);
3.风(feng)机变速及启停控制。
二、风机盘管(guan)系统的监控(kong)功能描述
1、风(feng)机(ji)变速及(ji)启(qi)(qi)停(ting)控(kong)(kong)制,为(wei)调节(jie)风(feng)量(liang),目前几乎所(suo)有风(feng)机(ji)盘管(guan)的(de)风(feng)机(ji)都(dou)采(cai)用高(gao)、中、低(di)3档实现风(feng)机(ji)的(de)转速控(kong)(kong)制。启(qi)(qi)停(ting)控(kong)(kong)制、风(feng)量(liang)调节(jie)通(tong)常是使用者就地手动控(kong)(kong)制。
2.室温(wen)(wen)(wen)控(kong)制(zhi),室温(wen)(wen)(wen)控(kong)制(zhi)是一个完全的负反馈温(wen)(wen)(wen)控(kong)系统。它由(you)室温(wen)(wen)(wen)控(kong)制(zhi)器及电动阀组(zu)成,通过(guo)调节(jie)冷、热(re)水(shui)量(liang)(liang)而改变盘(pan)管的供(gong)冷或(huo)供(gong)热(re)量(liang)(liang),控(kong)制(zhi)室内(nei)温(wen)(wen)(wen)度。
大多数风机盘(pan)管(guan)都是冬(dong)、夏共享的(de)(de)。因此(ci),在其温(wen)控器上有(you)冬(dong)夏转(zhuan)(zhuan)换的(de)(de)措施。冬(dong)夏转(zhuan)(zhuan)换的(de)(de)措施有(you)手动(dong)和自动(dong)两种方式,应根据系(xi)统(tong)形式及使用要求来(lai)决定(ding)。
(1)温控(kong)器手动转(zhuan)换(huan)(huan)。在(zai)各个(ge)温控(kong)器上设置冬、夏(xia)季(ji)手动转(zhuan)换(huan)(huan)开(kai)关,使得(de)夏(xia)季(ji)时供(gong)冷运(yun)行,冬季(ji)时供(gong)热(re)运(yun)行。当(dang)温控(kong)器为位式控(kong)制器时,它与冬、夏(xia)手动转(zhuan)换(huan)(huan)开(kai)关的接线。
夏(xia)季时转换开关拨向“S’’,如果室温(wen)过高,则温(wen)感组件向前动作(zuo),使(shi)温(wen)控器节点(dian)1, 2接(jie)通,电(dian)动水(shui)阀(fa)带电(dian)打开;当室温(wen)降(jiang)低(di)后(hou),温(wen)感组件向后(hou)动作(zuo),使(shi)1, 2节点(dian)断开,电(dian)动水(shui)阀(fa)失电(dian)后(hou)由弹簧复位而关闭(bi)。
在(zai)冬(dong)季(ji)时(shi),把转(zhuan)换开关(guan)手动(dong)拨向“w”挡,其他动(dong)作过(guo)程与上述类似,但动(dong)作方向与夏季(ji)相反,即室温(wen)过(guo)高(gao)时(shi)关(guan)水阀(fa),室温(wen)过(guo)低时(shi)开水阀(fa)。
(2)统一区(qu)域手动转换(huan)。对于同(tong)一朝向或相同(tong)使用功(gong)能的风(feng)机盘管,如果管理(li)水平较高(gao),也(ye)可(ke)(ke)以把转换(huan)开关(guan)统一设(she)置,集中进行冬、夏工况的转换(huan),这样各温控(kong)器上可(ke)(ke)取消就(jiu)地操作的转换(huan)开关(guan)。
注意这种方式要(yao)求所有统一转换的风机盘管必(bi)须是同一电(dian)源,这需(xu)要(yao)与电(dian)气工种密切配合(he)。